| Availability: | |
|---|---|
| Quantity: | |
Full Safety Protection Configuration, Comply with Construction Electrical Standards
Each circuit is equipped with independent leakage circuit breaker, short-circuit and overload dual protection. The leakage action current is 30mA with 0.1s rapid power-off response, effectively preventing electric shock accidents. All live parts are isolated, with obvious high-voltage warning signs to avoid misoperation risks, fully meeting national construction site temporary electricity safety specifications.
Thickened Anti-corrosion Cabinet, Excellent Outdoor Weather Resistance
The cabinet body adopts 1.2mm thick cold-rolled steel plate, treated with pickling phosphating and orange-red/yellow electrostatic anti-rust spraying. The top has a sloped waterproof roof, and the door is fitted with full-circle rubber sealing strips to reach IP33 protection grade. It resists rain, dust and ultraviolet rays, and can work stably outdoors all year round without rusting within 5 years.
Modular Custom Circuit Layout, Flexible Matching Multiple Loads
Support customized one-level, two-level and three-level distribution schemes. We can freely configure watt-hour meters, industrial plugs, air switches and branch circuits according to customer's construction equipment power demand. The internal busbar adopts color-coded copper bars (yellow-green-red-blue) for clear wiring, convenient for later inspection and maintenance.
Detachable Mobile Bracket Design, Easy On-site Transfer
Medium and small distribution boxes are equipped with foldable integrated metal stand, which can be directly placed on the construction ground without additional support. The lightweight cabinet design allows 1 worker to move it alone, greatly improving the turnover efficiency of temporary power supply for multi-stage construction projects.
Complete Standard Accessories, One-stop Delivery Without Secondary Assembly
All internal electrical components adopt well-known domestic brand breakers with stable quality. The box is pre-wired and fully tested in factory before delivery. Matching door lock, grounding copper bar, wiring terminal and rain cover are all equipped, customers only need to connect incoming and outgoing cables on site to put into use, saving construction preparation time.
| Technical Parameters |
| Item | Technical Specification |
| Product Name | Construction Site Temporary Distribution Box (1/2/3 Level) |
| Cabinet Material | 1.2mm Cold Rolled Steel Plate, Anti-rust Electrostatic Spraying |
| Protection Grade | IP33 |
| Rated Input Voltage | 380V Three-phase / 220V Single-phase |
| Rated Current Range | 63A / 100A / 160A / 250A / 400A Optional |
| Leakage Protection Parameter | 30mA operating current, ≤0.1s breaking time |
| Standard Color | Engineering Orange / Safety Yellow / Warning Red |
| Structure Type | Floor-standing with bracket / Wall-mounted double door / Portable small box |
| Applicable Ambient Temperature | -20℃ ~ +50℃ |
| Service Life of Cabinet Shell | 5 Years Anti-rust Guarantee |
| Optional Accessories | Watt-hour meter, industrial socket, status indicator light, rainproof cap |
| Product Uses |
◉ Construction Building Sites: Serve as the core temporary power supply for high-rise building projects. Match tower cranes, concrete mixers, welding machines and construction lighting, realize hierarchical power distribution to eliminate electric shock hidden dangers.
◉ Road & Bridge Engineering: Movable distribution boxes for highway, bridge and tunnel construction. The rainproof shell adapts to open-air wild working environment, convenient to transfer with construction progress.
◉ Municipal Renovation Projects: Used for urban road reconstruction, pipeline maintenance and landscape engineering. Small portable three-level boxes supply power for small electric tools such as cutting machines and drills.
◉ Outdoor Temporary Activities: Suitable for outdoor exhibitions, temporary construction camps and event sites. Multiple industrial socket ports can simultaneously supply power for various electrical equipment.
◉ Factory Workshop Temporary Power Supply: Provide temporary power distribution for workshop equipment maintenance, production line transformation, with fast installation and flexible layout.
| Product Operate Guide |
Check the cabinet door sealing, grounding wire and all circuit breakers before power-on. Confirm each leakage protector works normally via test button. Distribute loads evenly to balance three-phase current. Cut off all air switches and hang warning signs before maintenance. Download full English operation PDF for detailed temporary electricity safety operation rules.
| FAQ |
Q: Can this distribution box work in rainy open-air construction sites?
A: Yes. The sloped waterproof top and full rubber door sealing strips reach IP33 protection grade to prevent rainwater infiltration. We can add extra external rain covers for long-term outdoor open-air use to strengthen waterproof performance.
Q: Is the internal circuit layout customizable according to my equipment?
A: Full customization is supported. We can configure the quantity of main switches, branch circuits, industrial sockets and watt-hour meters according to your welding machines, cutting tools and lighting load, and provide free wiring layout drawing.
Q: What's the difference between Level 1, Level 2 and Level 3 distribution boxes?
A: Level 1 box is the main incoming power cabinet for overall power control; Level 2 is sub-distribution cabinet for large machinery; Level 3 is terminal portable box for hand-held small tools. We can supply matching sets of three-level boxes for complete construction power systems.
Q: Are the circuit breakers inside the cabinet replaceable?
A: All breakers adopt standard general specifications, easy to purchase replacement parts globally. The modular rail installation design allows quick disassembly and replacement without re-wiring.